EPA's Refrigerant Management regulations, 40 CFR Part 82 Subpart F, implement Section 608 of the Clean Air Act. They are designed to reduce emissions of ozone-depleting refrigerants and their substitutes from stationary refrigeration and air-conditioning equipment. The rules cover venting, technician certification, refrigerant sales, recovery equipment, leak repair, recordkeeping and disposal.
Facilities with large chillers, industrial process refrigeration, cold storage, supermarkets and commercial HVAC systems are most affected.
What Is Section 608?
Subpart F applies to ozone-depleting substances such as CFC and HCFC refrigerants, and many provisions also apply to substitute refrigerants such as HFCs. In addition, EPA's 2024 Emissions Reduction and Reclamation rule under the American Innovation and Manufacturing (AIM) Act, in 40 CFR Part 84, sets leak repair and other management requirements for appliances containing HFC refrigerants, phasing in from 2026. Because EPA has been revisiting parts of its AIM Act program, facilities should confirm the current status of these HFC requirements.
Who Must Comply?
- Owners and operators of refrigeration and air-conditioning appliances.
- Technicians who service, maintain, repair or dispose of appliances.
- Refrigerant wholesalers and reclaimers.
- Recovery equipment manufacturers.
- Final processors who dispose of small appliances.
Key Requirements
Venting prohibition
It is illegal to knowingly vent or release ozone-depleting refrigerants or their substitutes, such as HFCs, into the atmosphere while maintaining, servicing, repairing or disposing of appliances. De minimis releases during good-faith recovery are not violations. Certain substitutes, such as some exempt natural refrigerants, are not subject to the venting prohibition in specific end uses.
Technician certification
Technicians who open appliances must be certified by an EPA-approved program:
- Type I: small appliances.
- Type II: high-pressure and very high-pressure appliances.
- Type III: low-pressure appliances.
- Universal: all three types.
The sale of refrigerants, including HFCs, is generally restricted to certified technicians, with limited exceptions such as small cans for motor vehicle air conditioning.
Evacuation and recovery equipment
Before opening an appliance or disposing of it, technicians must evacuate refrigerant to specified levels using certified recovery or recycling equipment.
Leak repair for larger appliances
For appliances with 50 or more pounds of ozone-depleting refrigerant, owners and operators must calculate the leak rate each time refrigerant is added and repair leaks when the rate exceeds:
- 20% for commercial refrigeration.
- 30% for industrial process refrigeration.
- 10% for comfort cooling and other appliances.
Leaks must generally be repaired within 30 days of discovering the excess leak rate, with initial and follow-up verification tests. Extensions or retrofit and retirement plans are allowed in specific circumstances. Appliances that leak 125% or more of their full charge in a calendar year must be reported to EPA by March 1 of the following year. Periodic leak inspections apply to some appliances that exceeded the threshold.
Recordkeeping
Owners and operators of appliances with 50 or more pounds of refrigerant must keep records of servicing, refrigerant added, leak rate calculations, leak inspections and verification tests. Technicians must provide service invoices showing the amount of refrigerant added. Records are generally kept for 3 years.
Disposal
Refrigerant must be recovered before appliances are disposed of. For small appliances and similar equipment, the final person in the disposal chain must recover the refrigerant or verify, through a signed statement, that it was recovered earlier. Records of disposal of appliances with 5 to 50 pounds of refrigerant must be kept for 3 years.
Penalties and Enforcement
EPA enforces Section 608 through inspections, tips and record reviews. Penalties under the Clean Air Act are assessed per day per violation and are adjusted annually for inflation. Common enforcement issues include venting, uncertified technicians, unrepaired leaks and missing records at supermarkets and industrial facilities.
Common Compliance Mistakes
- Not calculating leak rates each time refrigerant is added.
- Missing the 30-day repair deadline or verification tests.
- Using contractors without checking technician certification.
- Incomplete service records from contractors.
- Disposing of appliances without verifying refrigerant recovery.
- Not tracking new HFC requirements under the AIM Act.
How to Comply: Step by Step
- Inventory appliances with their refrigerant type and full charge.
- Verify technicians hold the right certification.
- Track refrigerant additions and calculate leak rates every time.
- Repair and verify leaks above thresholds within required timelines.
- Keep records for at least 3 years.
- Report chronic leakers to EPA by March 1.
- Manage disposal with recovery verification.
- Monitor AIM Act requirements for HFC appliances.
How SMS360 Helps
SMS360's Audits & Inspections module schedules leak inspections and records results by appliance. The Document Library stores technician certifications, service invoices and leak rate calculations, and Actions Management tracks repairs and verification tests against deadlines.
Frequently Asked Questions
Is it illegal to vent HFC refrigerants?
Yes. The venting prohibition applies to ozone-depleting refrigerants and to most substitutes, including HFCs.
What leak rate triggers repair for comfort cooling?
10% for comfort cooling appliances with 50 or more pounds of ozone-depleting refrigerant.
How long must refrigerant records be kept?
Generally 3 years.
Who can buy refrigerant?
Generally only EPA-certified technicians, with limited exceptions.