A ground-fault circuit interrupter (GFCI) is a fast-acting electrical device that shuts off power when it senses an imbalance between the current flowing to and from a tool or appliance. That imbalance usually means current is leaking to ground, possibly through a person.
GFCIs are designed to trip when leakage reaches about 4 to 6 milliamps and to do so within a fraction of a second, fast enough to help prevent serious injury or electrocution. They do not protect against overloads or short circuits between conductors, which are handled by fuses and circuit breakers.
Types of GFCIs
- Receptacle GFCI: replaces a standard outlet and protects that outlet and sometimes downstream outlets.
- Circuit breaker GFCI: installed in the panel and protects an entire circuit.
- Portable GFCI: plugs into an outlet or is built into an extension cord, common on construction sites.
OSHA GFCI Requirements
Construction
Under 29 CFR 1926.404(b)(1), employers must protect employees on construction sites using either:
- GFCIs on all 120-volt, single-phase, 15- and 20-ampere receptacle outlets that are not part of the permanent wiring of the building or structure, or
- An assured equipment grounding conductor program, with a written program, a competent person, and regular testing of cords, receptacles and equipment.
General industry
In general industry, electrical safety rules at 29 CFR 1910.304(b)(3)(ii) require ground-fault protection for receptacles used during construction-like activities, such as maintenance, remodeling and repair involving temporary wiring. The National Electrical Code also requires GFCIs in many locations, such as wet or damp areas.
Testing a GFCI
- Plug a lamp or tester into the outlet and confirm power.
- Press the "Test" button. Power should shut off.
- Press "Reset" to restore power.
- If power does not shut off, the GFCI is not working and must be replaced.
Manufacturers typically recommend testing GFCIs monthly. Portable GFCIs on job sites should be tested before each use.
Common Mistakes to Avoid
- Assuming a GFCI protects against all electrical hazards.
- Using damaged extension cords downstream of a GFCI.
- Not testing GFCIs or ignoring repeated tripping.
- Relying on an assured grounding program without the required documentation.
How SMS360 Helps
SMS360's Audit Management module turns GFCI tests and cord inspections into quick mobile checklists with records for each site. Training Management tracks electrical safety training, and Actions Management assigns failed devices for replacement.
Frequently Asked Questions
At what current does a GFCI trip?
Personnel-protection GFCIs are designed to trip when ground-fault current reaches about 4 to 6 milliamps.
Are GFCIs required on construction sites?
Yes, unless the employer uses an assured equipment grounding conductor program that meets 29 CFR 1926.404(b)(1)(iii).
Does a GFCI replace grounding?
No. Equipment grounding and GFCIs work together. A GFCI adds a layer of protection for people.