An emergency eyewash and shower is equipment that delivers a controlled flow of water to flush the eyes, face or body after contact with corrosive or hazardous materials. Eyewash stations treat the eyes, drench showers treat the whole body, and combination units do both.
The first seconds after a chemical splash are the most important. Fast, thorough flushing can be the difference between a minor irritation and permanent eye damage or a serious burn.
OSHA Requirements
OSHA's Medical Services and First Aid standard, 29 CFR 1910.151(c), requires that where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing must be provided within the work area for immediate emergency use. Several substance-specific standards and the battery charging rules for powered industrial trucks include similar requirements.
OSHA's standard does not define "suitable," so OSHA and industry rely on the consensus standard ANSI/ISEA Z358.1 for design, installation and maintenance details.
Key ANSI/ISEA Z358.1 Requirements
- Location: reachable within 10 seconds, about 55 feet, on the same level as the hazard with an unobstructed path.
- Activation: the valve must activate in 1 second or less and stay open hands-free.
- Flushing time: a 15-minute supply of flushing fluid.
- Water temperature: tepid, between 60°F and 100°F (16°C to 38°C).
- Flow: at least 0.4 gallons per minute for eyewash units and 20 gallons per minute for drench showers.
- Signage and lighting: highly visible sign and a well-lit area.
- Weekly activation: activate plumbed units weekly to clear the line and verify flow.
- Annual inspection: inspect all units annually for compliance with the standard.
For strong acids or caustics, the station should be immediately adjacent to the hazard. Self-contained units must have their flushing fluid changed according to the manufacturer's instructions.
Eyewash Stations vs. Eyewash Bottles
Personal eyewash bottles can provide immediate flushing while a worker moves to a full station, but they do not meet the 15-minute flushing requirement and cannot replace a compliant eyewash station.
Common Mistakes to Avoid
- Blocking stations with pallets, carts or stored materials.
- Placing units behind doors or on a different floor.
- Skipping weekly activation, which allows bacteria to grow in stagnant lines.
- Supplying water that is too cold or too hot for 15 minutes of flushing.
- Not training workers to hold their eyes open and flush for the full time.
How SMS360 Helps
SMS360's Audit Management module makes weekly eyewash activations and annual inspections quick mobile checklists with photo evidence. Failed checks become tracked items in Actions Management, and Safety Data Sheets identify the chemicals that require emergency flushing in each area.
Frequently Asked Questions
How far can an eyewash station be from a hazard?
ANSI Z358.1 calls for a location that can be reached within 10 seconds, about 55 feet. For highly corrosive chemicals, it should be immediately adjacent.
How often should eyewash stations be tested?
Plumbed units should be activated weekly, and all units should be inspected annually for compliance with ANSI Z358.1.
How long should a person flush their eyes?
ANSI Z358.1 requires a 15-minute flushing supply. SDS first aid sections may recommend longer flushing for some chemicals.