An anchorage is a secure point of attachment for lifelines, lanyards or deceleration devices that form part of a personal fall arrest system (PFAS). It is the "A" in the ABCs of fall arrest: anchorage, body support and connectors. If the anchorage fails, every other part of the system fails with it.
Anchorages can be permanent, such as engineered roof anchors and horizontal lifeline systems, or temporary, such as beam clamps, cross-arm straps and concrete anchors installed for a single job.
OSHA Strength Requirements
OSHA's fall protection rules for construction (29 CFR 1926.502(d)(15)) and general industry (29 CFR 1910.140(c)(13)) set the same basic test. Anchorages used to attach a personal fall arrest system must be:
- Capable of supporting at least 5,000 pounds per employee attached, or
- Designed, installed and used as part of a complete personal fall arrest system that maintains a safety factor of at least two, under the supervision of a qualified person.
Anchorages for personal fall arrest systems must also be independent of any anchorage used to support or suspend platforms.
Positioning and restraint anchorages
Positioning systems, which hold a worker in place while leaving both hands free, require anchorages capable of supporting at least twice the potential impact load or 3,000 pounds, whichever is greater. Travel restraint systems prevent a worker from reaching an unprotected edge, so the anchorage must hold the restraint load rather than a fall.
Choosing and Locating an Anchorage
A strong anchor in the wrong place can still cause serious injury. When selecting an anchorage, consider:
- Location: ideally directly overhead to reduce free fall distance and swing.
- Fall clearance: the total distance needed below the worker, including free fall, deceleration distance, harness stretch, worker height and a safety margin.
- Swing fall: working far to the side of the anchor creates a pendulum effect that can slam the worker into a structure.
- Compatibility: connectors must be compatible with the anchor to prevent roll-out.
- Structure: pipes, conduit, handrails and light fixtures are not anchorages unless evaluated and approved.
Inspection and Maintenance
Anchorages should be inspected before each use for corrosion, deformation, cracking, loose fasteners and damaged webbing. Permanent anchors are typically inspected and recertified on a schedule set by the manufacturer and a qualified person. Any anchorage that has arrested a fall should be removed from service until evaluated.
Common Mistakes to Avoid
- Tying off to guardrails, conduit or ductwork that was never rated.
- Ignoring swing fall and clearance when placing an anchor.
- Reusing temporary anchors beyond the manufacturer's limits.
- Missing documentation for engineered anchors and horizontal lifelines.
- Attaching more workers than the anchorage is rated for.
How SMS360 Helps
SMS360's Audit Management module lets teams build anchorage and fall protection inspection checklists, attach photos, and turn failed items into tracked actions. Training Management records which workers are trained as authorized users or competent persons, and the Document Library stores anchor certifications and rescue plans so they are easy to find on site.
Frequently Asked Questions
How much weight must a fall protection anchor hold?
OSHA requires 5,000 pounds per attached employee, unless the anchorage is part of a complete system designed by a qualified person with a safety factor of at least two.
Can a guardrail be used as an anchorage?
Generally no. Guardrails are designed to resist a 200-pound force, not a fall arrest load. Only use a structure that has been evaluated and approved as an anchorage.
How often should anchorages be inspected?
Users should inspect anchorages before each use. Permanent anchorages should also receive periodic formal inspections according to the manufacturer and a qualified person.